C2C: The New 40-80 A Automatic Transfer Switch
How can the power supply be switched when the main source fails? Telergon’s new C2C Automatic Transfer Switch (ATS) enables automatic transfer between two power sources and retransfer to the main supply. Available in 40, 63 and 80 A ratings, it expands our range of solutions for power supply continuity.
What is an Automatic Transfer Switch and what is it used for?
An Automatic Transfer Switch, also known as an ATS, is a device that automatically switches the power supply to an installation between two sources.
Its function is to transfer loads to an alternative source when conditions requiring a changeover are detected. This helps restore the power supply without manual intervention.
Why is it important to automate switching between power sources?
Having an alternative power source is only part of the solution in the event of a power failure. It is also necessary to manage when and how that source is connected to the loads.
Automatic transfer reduces reliance on manual intervention and helps restore the power supply. This is particularly important in buildings, essential services and industrial installations, where a power outage can disrupt operations.
The ATS selected must be suited to the characteristics of the power sources, the loads and the operating requirements of each installation.
What functions does Telergon’s new C2C incorporate?
The C2C features automatic transfer and retransfer, managing the changeover between power sources I and II and the return to the main supply.
It also incorporates the following functions:
- Power source I voltage monitoring: single-phase or three-phase, depending on the configuration.
- Single-phase voltage monitoring of power source II.
- LED indication of switch position I and II: allows the connected power source to be identified at a glance.
These functions combine voltage monitoring and automatic switching in a single device.
What current ratings and versions is the C2C available in?
The C2C Automatic Transfer Switch is available in 40, 63 and 80 A ratings, with 1P+N, 3P and 3P+N versions.
This range allows the appropriate device to be selected according to the current rating and configuration of the installation. Its maximum weight is 0.8 kg for 1P+N, 0.9 kg for 3P and 1 kg for 3P+N.
What are the main technical specifications of the C2C?
The C2C series complies with IEC 60947-6-1, with PC classification and AC-33B utilisation category. It has an insulation voltage of 690 V and an impulse withstand voltage of 8 kV.
In terms of operation, it features a transfer switching time of 1.5 seconds and a contact transfer time of 1 second.
Its DIN rail mounting and manual/automatic selector make both installation and operation straightforward.
How do you choose the right Automatic Transfer Switch?
Selecting an ATS requires an understanding of the load current, the configuration of the power sources and the monitoring and control functions required by the project.
The C2C expands Telergon’s ATS range in the 40–80 A current rating range, providing a new, more efficient and compact solution for installations requiring automatic transfer and retransfer where space is limited.